Skip to main content

Table 3 Experimental results obtained when determining the total decay coefficient K

From: Modeling of residual chlorine in a drinking water network in times of pandemic of the SARS-CoV-2 (COVID-19)

Diameter (mm) Flow (m3 s− 1) Velocity (m s− 1) Length (m) K (h− 1)
250 0.0725 1.43 3075 0.226
200 0.0352 1.09 416 0.222
200 0.0219 0.675 3380 0.219
160 0.0304 1.51 1817 0.271
110 0.0003 0.10 2535 0.157
63 0.0009 0.11 2510 0.159